Quick Detail
Place of Origin
HS-CODE
84-
Package & Delivery Lead Time
Detailed Description
1.SPECIFICATIONS OF GEN-SET
1.1
SET MODEL
60KVA
1.2
Prime at 50HZ,40℃ ambient
44KW 55KVA
1.3
Standby at 50HZ, 40℃ ambient
48KW 60KVA
1.4
Rated Gen-set output
230/400V 50HZ
1.5
Rated Relative humidity
≤ 60%
1.6
Dimension(L×W×H)
1780×850×1360mm
1.7
Weight
1100kg
1.8
Fuel consumption 100% prime load
10.7L/h
1.9
Total head radiated to ambient
16KW
1.10
Structure of Gen-set
The Gen-set adopt integrative structure,engine is fix on high strength steel basic frame,anti vibration instrument between the engine and basic frame,cooling fan have protecting cap,control cabinet and circuit breaker installed on Gen-set
1.11
Control system (Optional)
Basic control panel or Advanced control panel with automatically start-up function and other function
2.SPECIFICATIONS OF ENGINE
2.1
Engine Brand
Cummins
2.2
Engine Model
4BTA3.9-G2
2.3
Governor/Class
Electrical
2.4
Cylinder NO.
4
2.5
Engine build
Line
2.6
Fuel spray pattern
PT direct injection
2.7
Start-up method
24V, electric
2.8
Aspiration
Turbocharged/Aftercooled
2.9
Cooling mode
Radiator cooled (enclose water)
2.10
Bore and stroke
102×120 mm
2.11
Compression ratio
16.5:1
2.12
Displacement
3.9L
2.13
Engine Prime Power at 1500rpm
50KWm
2.14
Engine standby power at 1500rpm
55KWm
2.15
Battery capacity
100A/hr
2.16
Starting/Min temperature
4℃
2.17
Lubrication oil capacity
11L
2.18
Coolant capacity – radiator and engine (40℃)
28L
2.19
Exhaust temp – full load prime
488℃
2.20
Exhaust gas flow – full load prime
906m 3/h
2.21
Exhaust gas back pressure max
76mm Hg
2.22
Air flow – radiator (40℃ ambient)
2.1 m 3/s
2.23
Pusher fan head (duct allowance)40℃
10mmH 2O
2.24
Air intake – engine – full load prime
248m 3/h
2.25
Standard Air intake temp
25℃
2.26
Fuel type
#0 Diesel (Natural temperature)
2.27
Filter system
Adopt whole changeable lubricating oil,fuel filter and air filter
2.28
Exhaust system
Adopt industrial high efficiency muffler and ripple pipe