150KW /188KVA CUMMINS MARINE GENSET 50HZ COOLED BY HEAT EXCHANGER&SEA WATER PUMP WITH CCS
Cummins series marine main generator set and emergency set are provided, the power range from 20KW TO 1600KW, compact unit is easy to install, with low fuel consumption, good dynamic performance, high efficiency. The ship certificate of CCS, BV,NK or other major classification society can be provided.
- - - -
Generator Set Model: | CCFJ150J |
| |
Performance of Generator Set: | 220V,3phases,50Hz Output:150kw/188kva |
| |
Prime Output Power: | 150kw/188kva |
Rating Conditions: | In accordance with ISO-3046 reference conditions: |
-Air Pressure | 100 Kpa |
-Air Temperatur | 45 |
-Relative Humidity | 95% |
- Power Deration | Operation at elevated temperature for sustained operation above 45 , derate by 2% per 11 . |
Voltage | 30VAC |
Frequency | 50Hz |
Speed | 1500 RPM |
P.F. | 0.8 |
Phase/Wire | 3/3 |
| |
Governor Type: | ELECTRIC TYPE |
| 10 % |
| 5 % |
Recovery time | 5 s |
Frequency Variation Variation in Steady State | 3% |
Momentary Voltage Variation | 15,20 |
Voltage Regulation in Steady State | 2.5% |
Voltage Variation in Steady State | 3% |
Recovery time | 1.5 s |
| |
- - - -
- - - -
Engine Model: | NTA855-D(M) |
- Prime Rating | 180 KW @ 1500 RPM |
| |
General Configuration: | |
# No. of cycle | 4 |
| |
- Bore x stroke | 140 mm x 152 mm |
| |
| |
-Aspiration | Turbocharger , aftercooler |
| |
Performance data | |
| |
General Data | |
| |
Fuel System | |
-Maximum Allowed Restriction to Fuel Pump | 20 Kpa |
-Maximum Allowed Return Line Pressure | 8 Kpa |
-Fuel Consumption at rated power | 209g/kw.hr (engine only) |
| |
| |
- - - -
- - - -
Exhaust System | |
-Maximum Allowed Back Pressure | 10 K Pa (3 in. Hg) |
-Recommended New Engine Allowed Back Pressure | 5 K Pa (1.5 in. Hg) |
| |
Air Induction System | |
-Maximum Allowed Intake Restriction | 635 mm H2O |
| |
Lube Oil system | |
-Oil Pan Capacity, High/Low (Standard) | 36/28.4Liters |
| |
-Maximum Operational Angularity of Oil Pan | |
Front Down | 30 |
Front Up | 38 |
Side to Side | 38 |
| |
Electrical System | 24 V DC |
Starting system | 24VDC starting motor, 24VDC |
Cold start temperature | 0 |
| |
Operation Fluids & Lubricants: | |
Fuel Oil | Diesel Oil is Grade No. 2-D requirements of the American Society for Testing and Materials (ASTM) ,Or China Fuel Type 0 GB 252-8 (Grade 1 & Special Grade ) as equivalent, or China Fuel Type -10 GB 252-87 ( grade 1 & special grade ) as equivalent |
| |
Lube Oil | SAE 15W-40, Grade CE, CF-4/SG, CG-4/SH or CH-4/SJ |
| |
Coolant | 50-50 Ethylene Glycol/Water and Adequate concentration of DCA4 |
| 5 |
- - - -
- - - -
Main Alternator Model | | Cummins WUXI Stamford HCM434D HCM434D |
Configuration of Main Alternator | | Brushless Single bearing Air cooling |
| | |
Technical Data of Main Alternator | | |
- Capacity | KVA | 188 |
- p.f. | | 0.8 |
- Voltage | | 220VAC |
- Frequency | | 50 Hz |
- Insulation System | | H |
- Temperature rise | | F |
- Protection Class | | IP23 |
- Phase/Wire | | 3/3 |
- POLES | | 4 |
- - - -
Section C Supply Scope
MARINE GENERATING SET,CONSISTING OF ( PER UNIT)
G - DRIVE ENGINE, NTA855-D(M), WITH FOLLOWING EQUIPMENT:
1.1 AIR SYSTEM
# # AIR CLEANER
# TURBOCHARER
# AFTERCOOLER
1.1.4 CRANKCASE VENT LINE
1.2 COOLING SYSTEM
1.2.1 FRESH WATER PUM,CENTRIFUGAL TAPY
1.2.2 THERMOSTAT , FOR FRESH WATER
1.2.3 WATER FILTER
1.2.4 SEA WATER PUMP
1.2.5 HEAT EXCHANGER
1.3 LUB OIL SYSTEM
1.3.1 OIL PUMP
1.3.2 OIL FILTER
1.3.3 OIL COOLER
1.3.4 OIL DIPSTICK
1.3.5 OIL PAN
1.4 FUEL OIL SYSTEM
1.4.1 FUEL FILTER
1.4.2 FUEL PUMP WITH ELECTRIC GOVERNOR
1.4.4 FUEL/WATER SEPARATOR
1.4.5 FUEL INLET/OUTLET FLEXIBLE SECTION
1.5 EXHAUST SYSTEM
1.5.1 EXHAUST ELBOW
1.5.2 EXHAUST FLEXIBLE SECTION AS LOOSE
1.5.3 SPARKLESS MUFFLER AS LOOSE
1.5.4 FLANGE AS LOOSE
1.6 STARTING SYSTEM
1.6.2 24VDC START MOTOR
1.6.3 MOUNTED ALTERNATOR
2. ALTERNATOR HCM434C, HCM434C
2.1 AVR
2.2 SPACE HEATER , 220VAC
2.3 ONE POTENTIALMETER FOR VOLTAGE ADJUST AS LOOSE
# # CABLE GLAND
LOCAL CONTROL PANEL
3.1 OIL PRESS GAUGE
3.2 WATER TEMP. GAUGE
3.3 HOURMETER
3.4 FREQUENCY METER
3.5 POWER VOLTAGE
3.6 START/STOP SWITCH
3.7 EMERGNECY STOP BUTTON
3.8 TEST/RESET SWITCH
3.9 MONITORING SYSTEM:
MONITORING SYSTEM FOR
# RUN
# PRE-LOW OIL PRESSURE ALARM
# PRE-HIGH WATER TEMPERATURE ALARM
# OVERSPEED SHUTDOWN
# LOW OIL PRESSURE SHUTDOWN
# HIGH COOLANT TEMPREATURE
4. GENSET CONSTRUCTION:
- STRONG COMMON BASEKID
- ENGINE AND ALTERNATOR FLEXIBLE MOUNTING WITH ISOLATORS
- BATTERIES
5. QULIFICATION CERTIFICATE AND TEST REPORT
6. DRAWINGS AND DOCUMENT
6.1) 2 copies of the followings approval drawings & documents should be submitted within 4 weeks after signing the contract
# # Installation Drawings
# System Diagram
# Electrical drawings (includes customer interface)
# Technical sheet
# Outline drawing of loose supply accessory
6.2) 2 copies of working drawing &document should be submitted with 14 working days after received confirmation,( The approval drawing will be confirmed as working drawing if not received confirmation within 2 weeks )
6.3) One copy per genset of final document should be submitted while genset delivered
# # Specialist tools list,
# Parts catalog
# Operation and maintenance manual
# Engine test report
# Name plate&Control panel in English
7. ONE SET OF CUMMINS STANDARD TOOLS PER ENGINE, MADE IN CHINA