Detailed Description
11 kV - 3150kVA , Cast Resin Dry Type Transformer , Three Phases , Two Winding , Power Distribution
Advantages:
Cast resin dry typetransformer,eco-friendly, high efficiency.
# # Low loss, low noise, low partial discharge, high reliability. Fitfor general users , such as hospital, tower, hotel, etc.
# Strong capability withanti-short circuit, high anti-lightning impulse capability.
# HV coil is vacuum casted with epoxy resin with pressure, capabilities for better the cast without pressure. Subject to customer need, both HV and LV coil are fully vacuumed.
# Simulating analysis being used in the core model, the resonance can be avoided and the noise is reduced. Simulation calculation and analysis of lighting impulse wave are applied to the HV Coils; anti-lighting impulse capability is improved.
-----WHY CHOOSE US
` low noise, low loss and low partial discharge.
`Guarantee/warranty
Quality assurance18 months after delivery or 12 months after site operation, which comes earlier.
`High reputation
Wide exportation fromSouth Africa to South Asia, stable supply to Malaysia, Myanmar, Italy ..etc country ,with qualified certificateauthorized by KEMA, CESI, CTQC.
`Small order is also accepted
1 unit of transformer with minimum rated capacity of 100kVA.
`Experienced staff
Pearl Electric is national high-tech enterprise andowns more than 65expects and R&D engineers, over 2/3 of them have more than 3 years experience in technology and product developing. With such an pioneer army, Pearl devoted heart and soul on client's need to come up with perfect electriciy solution.
Cast resin dry type transformer
Care shall be taken to ensure that fittings are located so as not to interfere with the external connection to the bushing terminals, and the clearances to such connections shall not be less than the appropriate minimum phase-to-earth clearance given in column 2 of Table 2. The lines of approach of these connections may lie anywhere within the limits indicated in Figure 1, and the required phase-to- earth clearance shall apply at all points along these lines, as shown at the points marked 'L'. In addition, the minimum vertical working clearances from floor level to live metal shall be as listed in column 3 of Table
Table 2 Electrical clearances in air
- - - -
System highest voltage Um (kV) | Minimum phase-to-earth clearance 'L' (see note 1) (mm) | Minimum vertical working clearance from ground level to live metal (see note 2) ( mm) | 'X'-Dimension (2,5 x L) (*Min 3 000 mm) (mm) | 'Y'-Dimension (L + 3000) (mm) |
3,6 | 80 | 2 580 | 3 000 | 3 080 |
7,2 | 150 | 2 650 | 3 000 | 3 150 |
12 | 200 | 2 700 | 3 000 | 3 200 |
17,5 | 230 | 2 730 | 3 000 | 3 230 |
24 | 320 | 2 820 | 3000 | 3 320 |
36 | 430 | 2 930 | 3 000 | 3 430 |
48 | 540 | 3 040 | 3 000 | 3 540 |
72 | 770 | 3 270 | 3000 | 3 770 |
100 | 840 | 3 340 | 3 000 | 3 840 |
145 | 1 200 | 3 700 | 3 000 | 4 200 |
1) Dimension not applicable to standard bushings per se |
2) The minimum distance from the transformer base or ground level to the flange base of a bushing (or surge arrester) shall be 2 500 mm. |
- - - -
- - - -
No. | Items | Unit | PEC-S-kVA/HV/LV |
I Basic Information | | |
1 | Rated Voltage ratio | kV | 11kV / 0.433 kV |
1.01 | Rated Capacity | kVA | 3150 |
II Electric Performance | | |
2.01 | Rated Power | kVA | 3150 |
2.02 | HV | kV | 11 |
2.03 | LV | kV | 0.433 |
2.04 | Frequency | Hz | 50 |
2.05 | Number of phase | | Three |
2.06 | Insullation Class | | Class H |
2.07 | Temperature Rise (@40 ambient temperature) | K | 125K |
2.08 | Cooling Method | | AN |
2.09 | Tapping Ranging | | 2*2.5% |
2.1 | Vector Group | | Dyn11 |
2.11 | Noise level | dB | 61 |
2.12 | Impedance | % | 7 |
2.13 | No-load loss | W | 4500 |
2.14 | Load Loss (@120) | W | 23500 |
2.15 | Local Partial discharge | pC | <10PC |
2.16 | Impulse Withstand Voltage (HV/LV) | kV | 75/0 |
2.17 | Power Frequency Withstand Voltage
(HV/LV) | kV | 28/3 |
2.18 | Rated Duration of Short Circuit | s | 2 |
- - - -
2 Applied Standard
GB/T10228 , GB1094.11 , IEC60076-11 , DIN42523