11kV - 800kVA Cast Resin Dry Type Transformer , Three Phases , Two Winding , Power Distribution
Advantages:
# # Low loss, low noise, low partial discharge, high reliability.
# Strong capability withanti-short circuit, high anti-lightning impulse capability.
# HV coil is vacuum casted with epoxy resin with pressure, capabilities for better the cast without pressure.
# Simulating analysis being used in the core model, the resonance can be avoided and the noise is reduced. Simulation calculation and analysis of lighting impulse wave are applied to the HV Coils; anti-lighting impulse capability is improved.
Enclosure
The standard transformers with IP-classprotective enclosureis IP20. Subject to client need , wecan also provide IP30 toIP40 . Enclosure material is made by common steel plates,stainless steel plants or aluminium alloy and can be acid-washed,parkerised and powder-painted.
Temperature controller
The temperature controller can beinstalled on transformer body or on the wall of enclosure,which are reliable and convenient for users to check.
Safe operation and working life of power transformers depends largely on the safety and reliability of transformer winding. If the temperature of transformer winding exceed the temperature which insulation withstand, it will damage the insulation. This is one of the most important reasons that transformers cannot operate normally.
LD-B10 series temperature controller of dry transformer (Referred to as temperature controller) is an intelligent controller designed especially for safe operation of dry transformer. The temperature controller features adoption of single chip computer technology and utilization of the platinum thermo-resistors embedded in the winding of the dry transformer for detection and of temperature rise of the transformer windings. It can start or stop the cooling fan automatically for forced air cooling of windings and control over-temperature alarm and over-temperature tripping output so that the transformer will be operated safely.
Cast Resin Dry Type Transformer, Low Noise, Low Loss and Low Partial Discharge.
- - - -
No. | Items | Unit | |
I Basic Information | | |
1 | Rated Voltage ratio | kV | 11kV / 0.433 kV |
1.01 | Rated Capacity | kVA | 800 |
1.02 | Applicable Standards | | IEC 60076 |
1.03 | Manufacturer | | Pearl Electric |
1.04 | Country of Origin | | China |
II Electric Performance | | |
2.06 | Insullation Class | | Class H |
2.07 | Temperature Rise (@40 ambient temperature) | K | 125K |
2.08 | Cooling Method | | AN |
2.09 | Tapping Ranging | | 2*2.5% |
2.1 | Vector Group | | Dyn11 |
2.11 | Noise level | dB | 48 |
2.12 | Impedance | % | 4 |
2.13 | No-load loss | W | 1630 |
2.14 | Load Loss (@120) | W | 8300 |
2.15 | Local Partial discharge | pC | <10PC |
2.16 | Impulse Withstand Voltage (HV/LV) | kV | 75/0 |
2.17 | Power Frequency Withstand Voltage
(HV/LV) | kV | 28/3 |
2.18 | Rated Duration of Short Circuit | s | 2 |
III Materials & Accessories | | |
3.01 | Core Materials | | Silicon Steel Sheet |
3.02 | Winding Materials | | Copper conductor/foil |
3.03 | Insulation methods | | HV vacuum cast / LV impregnant |
3.04 | Main Insulation Materials | | Epoxy Resin |
3.05 | Tap-changer | pcs | Off-load tap-changer |
3.06 | Sensor for Temperature Alarm and Trip | pcs | Yes, contact provided |
3.07 | Protective Enclosure | pcs | IP00 |
- - - -
Applied Standard
GB/T10228 , GB1094.11 , IEC60076-11 , DIN42523