Site conditions | Motors are suitable for most working environment at temperature from -15°C t0 +40°C and altitude below 1000 meters |
Insulation | The motors' insulation system is set to Class F(105K), examined by Class B(80K), which ensure the life span and reliability of the motors. |
Motor protection | Motors can be installed with PTC, PT100 used as winding and bearing temperature measurement on request. |
Voltage and frequency | Standard voltage and frequency is 380V 50HZ, and can be set to any single voltage in the range of 200-660V at a frequency of 50 or 60HZ. The motors work well within variations of ±5% from the rated voltage. |
Vibration | Motors are designed to vibration class A, vibration class B is available on request. |
Duty | Continuous(S1) |
Cooling and ventilation | The standard cooling method is totally enclosed fan cooled(TEFC) in accordance with IC411 of IEC60034-6. Standard motors are equipped with auxiliary plastic fans. |
Winding | 100% Cooper Wire |
Protection class | The standard protection class is IP54/IP55, which can be used in humid and dusty environment. Higher degrees of protection is available. |
Quality assurance | From the first line of production designing till the finishing procedure, obey ISO9001 documented quality system. |