WEIGHTS AND MEASUREMENTS
|
||||||
CONDUCTOR SIZE (AWG/kcmil)
|
INSULATION THICKNESS (mils)
|
NOMINAL 0.D (mils)
|
AMPACITIES*(AMPS)
|
APPROX NET WEIGHT PER 1000 ft (lbs)
|
||
60℃
|
75℃
|
90℃
|
||||
8
|
60
|
258
|
30
|
40
|
45
|
36
|
6
|
60
|
293
|
40
|
50
|
60
|
49
|
4
|
60
|
337
|
55
|
65
|
75
|
65
|
2
|
60
|
392
|
75
|
90
|
100
|
94
|
1
|
80
|
463
|
85
|
100
|
115
|
126
|
1/0
|
80
|
500
|
100
|
120
|
135
|
151
|
2/0
|
80
|
540
|
115
|
135
|
150
|
182
|
3/0
|
80
|
587
|
130
|
155
|
175
|
221
|
4/0
|
80
|
639
|
150
|
180
|
205
|
269
|
250
|
95
|
714
|
170
|
205
|
230
|
326
|
300
|
95
|
764
|
190
|
230
|
255
|
381
|
350
|
95
|
810
|
210
|
250
|
280
|
435
|
400
|
95
|
853
|
225
|
270
|
305
|
488
|
500
|
95
|
930
|
260
|
310
|
350
|
595
|
700
|
110
|
1101
|
310
|
375
|
420
|
829
|
750
|
110
|
1132
|
320
|
385
|
435
|
881
|
1000
|
110
|
1284
|
375
|
445
|
500
|
1145
|
* Ampacities based on CEC Part 1, Table 4 for not more than three conductors in raceway. For underground installations, refer to CEC, Rule 4-004 for Ampacity rating.
*All values are nominal and subject to correction
|