Packaging Details: | Packaging PE bag & Hard paper box Size of carton:51x41x39cm 40~50pcs/CTN lxc7220 |
---|---|
Delivery Detail: | 1day |
LXC7220 Completely replaced GU320B genset starting controller
Photos---------
Description----------
Control function automatically switches mains power monitoring and mains/power generation added to the LXC7210 based on(AMF),especially suitable for stand-alone automated systems.Its main features are as follows:
*32-bit ARM mircrocontroller,hardware integration and high reliablity have been further enhanced.
*The oversized LCD LCD240*128,with backlight,Chinese,English and other languages optional interface operation.All parameters can be set on the controller,convenient debugging personnel test machine.
*Of Things Internet through GPRS mobile network and the Internet,in any network can remote monitoring.
*Particularly for the management of the leasing industry provide the perfect solution:remote management via PC leased units Monitor all operating parameters(oil pressure,water temperature,voltage,current,power,etc.)can change the configuration at any time to protect inappropriate application of the unit,recorded 200 detailed fault information,including:time to failure,because,when the key parameters of voltage,current,power,oil pressure,water temperature,etc,and etc.,and at any time can be uploaded to the monitoring machine.Another multi-level password management items to facilitate the lease management.
*RS485 communication interface, using the MODBUS protocol can achieve "three remote" function.
*Control and protection functions: diesel or natural gas generator sets, automatic start / stop, sub-gate (ATS switch)Perfect failure protection.
*Parameter setting: Allow user to change the setting of its parameters, PC can be directly connected via USB controllerSettings. Memory in the internal FLASH memory when the system is powered down, it will not be lost.Note: All parameters can be adjusted from the front panel of the controller.
*SMS function, the alarm signal when the generator set alarm can be automatically sent to the set of five phone numbers Interest via SMS to control the generator set and generator set access state; using a PC via RS232 ,RS485 interface adjustments queries via the Internet using a PC (need to connect the DTU).
*A variety of temperature, pressure, oil level sensor curves can be used directly, and can be custom sensor curve.
*A variety of starting conditions (speed sensors, hydraulic, power generation) to select.
*Fault history, real-time clock, timer switch (monthly / weekly / daily boot time and can be set whetherWith load) functionality.*All output ports are relay outputs.
*Mains overvoltage, undervoltage, over frequency, under frequency, phase loss, reverse phase sequence function, power generation has overvoltage, undervoltage, over
Frequency, under frequency, over-current, over-power, reverse power, phase loss, reverse phase sequence function.
*Three fixed analog sensors (temperature, oil pressure, liquid level).
*Two programmable analog sensor can be set to a temperature or pressure or liquid level sensor.
*Wide power supply range (8 to 35) VDC, able to adapt to different starting battery voltage environments.
*Pump unit can be used, but also can be indicating instrument (only indication, alarm, the relay no action).
*Between the shell and the control panel design can reach IP55 waterproof rubber sealing rings of.
Working voltage | 8.0-35Vdc continuous |
Alternator votage input:Three-phrase four wire | 20V AC-360VA(ph-N)3 Phase 4 wire |
Three-phrase three wire | 30V AC-620V AC(ph-ph)3 Phase 3 wire |
Single-phrase two wire | 20V AC-360V AC(ph-N) |
Two-phrase three wire | 20V AC-360V AC(ph-N) |
Overall Power Consumption | <3W(Standby mode:<=2W) |
AC generator frequence | 50/60HZ |
Speed Sensor voltage Vpp | 1.0-70V(Peak to Peak) |
Speed Sensor frequence | 10,000 Hz (max) |
Starting relay output | The 16Amp controller power supply voltage output |
Fuel relay output | The 16Amp controller power supply voltage output |
Programmable relay outputs 1 | 7Amp 250VAC passive output |
Programmable relay outputs 2 | 7Amp 250VAC passive output |
Programmable relay outputs 3 | 16Amp 250VAC passive output |
Programmable relay outputs 4 | 16Amp 250VAC passive output |
Programmable relay outputs 5 | The 7Amp controller power supply voltage output(LXC7220) |
Programmable relay outputs 6 | The 7Amp controller power supply voltage output(LXC7220) |
Body Size | 210mm*152mm*48nn |
The size of holes | 186mm*141mm |
Current transformer secondary current | Specified 5A |
Working condition | Temperature:(-25-+70degrees)humidity:(20-90)% |
Storage Conditions | Temperature:(-40-+80degrees) |
Protection class | IP55:when the installation of waterpoof rubber ring between the controller and the control panel. |
IP42:when the installation of waterpoof rubber ring between the controller and the control panel does not. | |
Dielectric Strength | Object:Between the input/output/power |
Reference standard:IEC688-1992 | |
Test Methods:AC1.5kV/1min Leakage current:3mA | |
Weight | 0.68kg |