High Frequency Online UPS Rack Mount 220/230/240Vac (Rack Mount Star Series 1K-10KVA)
Key Features:
1)Protection against all types of power problems
2)LED/LCD Indicators display Detailed Real-Time UPS Status and parameters.
3)Set Output Voltage, Frequency parameter and bypass function on the display.
4)Auto Self-Testing System whileTurning on UPS
5)Wide input voltage range, Zero transfer time
6)the user can easily get UPS status information, including the working mode
7)Fan speed auto control when loads varies
8)Intelligent slot available
9)Provide intelligent slot, Provide standard battery pack
10)Input L and N lines reverse wiring detection, Auto start when AC back.
11)excellent electrical performance
12)Humanization bypass output, can be adjustable.
13)Smart RS232 communication with monitoring software
Applications RM Series 1KVA~10KVA High Frequency Rack Mount Online UPS is specially designed forservers, Data-center, critical network devices, Sensitive electronic equipment, Telecom,Transmission equipment,Mobile communication,Microwave communication,public security, ATM etc.
Technical Specification
Model |
RM1K |
RM2K |
RM3K |
RM1KL |
RM2KL |
RM3KL |
RM6KL |
RM10KL |
Rated Power |
VA/W |
1Kva/ 0.8Kw |
2Kva/ 1.6kw |
3Kva/ 2.4Kw |
1Kva/ 0.8Kw |
2Kva/ 1.6Kw |
3Kva/ 2.4Kw |
6Kva/ 4.8Kw |
10Kva/ 8Kw |
Input |
Phase |
Single Phase with Ground |
Nominal Voltage |
110115//120Vac or 220/230/240Vac |
220/230/240Vac |
Voltage Range |
60-138VAC or 115 ~ 300VAC |
176 ~ 276VAC |
Frequency Range |
46 ~ 54Hz(default), user adjustable within 40~60Hz |
46 ~ 54Hz |
Power Factor |
0.97 |
0.98 |
Connection |
IEC320-10A inlet |
IEC320-16A inlet |
IEC320-10A inlet |
IEC320-16A inlet |
Terminal Block |
Output |
Phase |
Single Phase |
Voltage |
110/115/120Vac or 220/230/240VAC ± 2% |
110/115/120Vac or 220/230/240VAC± 1% |
Frequency |
46~54Hz or 50Hz ± 0.2Hz (Line mode) |
46~54Hz (Line mode) |
50Hz ± 0.2Hz ( Battery mode) |
50Hz ± 0.05Hz ( Battery mode) |
Waveform |
Pure Sine Wave |
Overload Capability |
108%~150% for 30 sec., 150% for 300 ms |
105%~130% for 10 min.,130% for 1 min. |
Current Crest Ratio |
3:01 |
Connections |
IEC320 - 10A * 4 |
IEC320-10A and Terminal Block |
IEC320 - 10A * 4 |
IEC320-10A and Terminal Block |
IEC320-10A * 4 and Terminal Block |
Bypass |
Auto Transfer |
on overload and UPS failure |
Before UPS Power-on |
Default "NO", user adjustable to "YES" |
Yes |
Voltage Rangee |
80~264VAC (Default), user adjustable within 80~286VAC |
176 ~ 261VAC |
Transfer Time |
0 ms; less than 4 ms from inverter to bypass and vice versa |
Zero |
LED&LCD indicators |
Load level / Battery level, Battery , Utility Power, Inverter, Bypass, Overload, Fault |
Audible Alarm |
Bypass, On battery mode, Battery low, Overload, Fault |
Communications |
RS-232 Serial Interface |
Intelligent Slot; |
OPTIONS: WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC) |
Network Surge Protection |
RJ45 I/O port available for network or Fax/Modem |
Environmental |
Operating Temperature |
0 ~ 40°C |
Operating Humidity |
20 ~ 90% non-condensing |
Main Unit |
Net Weight (Kg) |
16.3 |
10.3 |
11.2 |
9.1 |
11.5 |
12.3 |
18.3 |
20.3 |
Dimensions (W x D x H) mm |
482 x 420 x 88 (2U) |
482 x 420 x 88 (2U) or (3U Internal Batteries |
482 x 420 x 88 (2U) |
482.6 x 600 x 130 (3U) Optional 4U |
Battery Pack |
Type |
Internal Batteries |
|
Nominal DC Voltage |
24/36VDC |
72/96VDC |
24/36VDC |
72/96VDC |
192/240VDC |
Battery Numbers & Capacity |
2/3Pcs *12V9Ah |
6/8Pcs*12V7.2Ah |
Depending on the capacity of external battery packs |
Backup Time (Full load) |
5min |
9min (with 1 BP) |
5min (With 1BP) |
Recharge Time |
5hrs to 90% |
Charging Current (Max.) |
1.0A |
8A±1A |
4.2A |
Charging Voltage |
27.4/41.1Vdc±0.6V |
110Vdc±0.4V |
41.1Vdc±0.6V |
110Vdc±0.4V |
274Vdc±1%V |
Net Weight (Kg) |
--- |
25.3 |
25.3 |
--- |
--- |
--- |
--- |
Dimensions (W x D x H) mm |
--- |
482 x 420 x88(2U) |
--- |
--- |
--- |
--- |