Quick Detail
Place of Origin
Brand Name
EuroKlimat
Model Number
EKAC 220BR1
HS-CODE
83-
Package & Delivery Lead Time
Package
Carton
Delivery Lead Time
20 working days after received your payment
Detailed Description
63 kW Air cooled modular chiller heat pump unit with environment friendly refrigerant model
Specifications:
Technical data sheet
- - - -
Model | | EKAC 220BR1 | EKAC 440BR1 | EKAC 660BR1 | EKAC 880BR1 | EKAC 1100BR1 | EKAC 1320BR1 |
Unit combination | Master unit | EKAC 220BR1M | EKAC 220BR1M | EKAC 220BR1M | EKAC 220BR1M | EKAC 220BR1M | EKAC 220BR1M |
slave unit | -- | EKAC 220BR1S | 2EKAC 220BR1S | 3EKAC 220BR1S | 4EKAC 220BR1S | 5EKAC 220BR1S |
Nominal cooling capacity | kW | 63 | 126 | 189 | 252 | 315 | 378 |
USRT | 17.92 | 35.84 | 53.76 | 71.68 | 89.6 | 107.52 |
104kcal/h | 5.42 | 10.84 | 16.26 | 21.68 | 27.1 | 32.52 |
Nominal heating capacity | kW | 68 | 136 | 204 | 272 | 340 | 408 |
USRT | 19.34 | 38.68 | 58.02 | 77.36 | 96.7 | 116.04 |
104kcal/h | 5.85 | 11.7 | 17.55 | 23.4 | 29.25 | 35.1 |
Total power of nominal cooling capacity | kW | 19.0 | 38 | 57 | 76 | 95 | 114 |
Total power of nominal heating capacity | kW | 19.8 | 39.6 | 59.4 | 79.2 | 99 | 118.8 |
Power supply | | 380V/3N~/50Hz |
Refrigerant | Type | | R410A |
Control | | Electronic expansion valve |
Compressor | Type | | Fully hermetic volute compressor |
Lubricant | | Grease (POE-160SZ) |
Qty. | Set | 2 | 4 | 6 | 8 | 10 | 12 |
Fan | Type | | High-efficiency vacuum braze-welded panel type |
Qty. | Set | 2 | 4 | 6 | 8 | 10 | 12 |
Water side heat
exchanger | Type | | High-efficiency vacuum braze-welded panel type |
Water flow for
cooling | m3/h | 10.8 | 21.6 | 32.4 | 43.2 | 54 | 64.8 |
Water flow rate
in heating mode | 3
m /h | 11.7 | 23.4 | 35.1 | 46.8 | 58.5 | 70.2 |
Water resistance | kPa | 43 | 43 | 43 | 43 | 43 | 43 |
Recommended diameter for general inlet/outlet water pipe | inch | 2 | 3 | 3 | 4 | 4 | 5 |
Power cable specification | Section area of live line | 2
mm | 10 | 35 | 70 | 95 | 120 | 150 |
Qty. of live lines | | 3 |
Section area of null line | 2
mm | 4 |
Qty. of null lines | | 1 |
Section area of grounding line | 2
mm | 10 | 16 | 35 | 50 | 60 | 75 |
Qty. of grounding lines | | 1 |
Dimensions | L x H | mm | 20121840 |
Width | mm | 880 | 2125 | 3370 | 4615 | 5860 | 7105 |
Unit weight | Net weight | kg | 515 | 1030 | 1545 | 2060 | 2575 | 3090 |
Operating weight | kg | 525 | 1050 | 1575 | 2100 | 2625 | 3150 |
- - - -
Note:
Test conditions for nominal cooling capacity: outlet water temperature 7C; water flow: 0.172m3/(hkw); outdoor ambient temperature 35C.
Test conditions for nominal heating capacity: outlet water temperature 45C; water flow: 0.172m3/(hkW); outdoor dry/web bulb temperature
7C/6C.
Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y-shaped filter.
Main Pipes of combined units need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK
does not provide the pipes.
Modular units can be formed using the 1 - 16 basic modules of same type or of different types as per practical needs. The above table lists
the parameters for common module combinations.
For on-site electric wiring, see the name plate or installation menu of the unit.
Decription
1. The unit uses environment friendly refrigerant R410A. The R410A refrigerant does not cause any ozone depletion. The heat exchange performance is excellent, improving the COP.
Less refrigerant is used, reducing the green house effect.
2. The unit features an efficient scroll compressor and heat exchanger. Modules of the system are best matched to improve heat exchange efficiency. The unit uses efficient and environment friendly refrigerant R410A, providing a higher COP. Multi-loop compressors are used to provide multiple capacity adjustment gears. This reduces startup current and electric investment. Excellent COP greatly reduces energy consumption and operation cost.
3. Before powering on and turning on the unit, you just need to connect the water pipe of each module to the main water pipe. A special access door is provided so that any inter parts of the unit can be conveniently serviced.
4 A low-sound fan generates little operation sound and vibration.
R410A scroll compressor generates little operation sound and vibration.
A flexible installation base further reduces operation vibration.
Air outlet pipes of the compressor are optimized to reduce vibration passed to the unit.
Advantage
The modular air-cooled heat pump unit with environment friendly refrigerant model uses new-generation R410A refrigerant which does not cause ozone depletion. The unit features optimized system design and an excellent COP. The unit is not only cost effective but also environment friendly,
easy to operate, reliable in performance, and can be installed flexibly. Therefore, units of this series are widely used in dining halls, bars, hotels, offices, top-tier clubs, hospitals, etc.