EMT(Electrical Metallic Tubing) Dimensiions and Weights
|
||||||||
Nominal Diamension
|
Outside Diameter
|
Wall Thickness
|
Length
|
Weight
|
||||
|
Size
|
Size
|
|
|
||||
Inch
|
mm
|
Inch
|
mm
|
Inch
|
mm
|
FT
|
mm
|
KG/Meter
|
1/2"
|
16
|
0.706
|
17.93
|
0.042
|
1.07
|
10
|
3050
|
0.439
|
3/4"
|
21
|
0.922
|
23.42
|
0.049
|
1.24
|
10
|
3050
|
0.669
|
1"
|
27
|
1.163
|
29.54
|
0.057
|
1.45
|
10
|
3050
|
0.99
|
1-1/4"
|
35
|
1.51
|
38.35
|
0.065
|
1.65
|
10
|
3050
|
1.469
|
1-1/2"
|
41
|
1.74
|
44.2
|
0.065
|
1.65
|
10
|
3050
|
1.698
|
2"
|
53
|
2.197
|
55.8
|
0.065
|
1.65
|
10
|
3050
|
2.17
|
2-1/2"
|
63
|
2.875
|
73.03
|
0.072
|
1.83
|
10
|
3050
|
3.177
|
3"
|
78
|
3.5
|
88.9
|
0.072
|
1.83
|
10
|
3050
|
3.879
|
3-1/2"
|
91
|
4
|
101.6
|
0.083
|
2.11
|
10
|
3050
|
5.17
|
4"
|
103
|
4.5
|
114.3
|
0.083
|
2.11
|
10
|
3050
|
5.75
|
Type
|
Labor
|
Weight
|
Material cost
|
RMC
|
1.0
|
1.0
|
1.0
|
Aluminum
|
0.89
|
0.34
|
0.99
|
IMC
|
0.89
|
0.76
|
0.84
|
EMT
|
0.62
|
0.42
|
0.35
|
PVC
|
0.55
|
0.2
|
0.43
|
Exact ratios of installation labor weight and material cost vary depending on the site of conduit, but the value for 3/4 inch (21metric) trade size are representative.
|