Applications:
Series ZY high vacuum insulating oil purifier is specially designed for purification of aging transformer oil, mutual inductor oil, switch oil, capacitor oil as well as for other electrical insulating liquids. The process maintains the oil's dielectric strength, removes free, soluble water, airgases and particulate matter.
Series ZY is efficient and economical insulating oil purifier. Doplex-Stereo film evaporation technology, unique and advanced dewatering, degassing components, making working efficiency is 3-5 tims than traditional oil purifier. Machine adopts interlocked protective system, double-infrared liquid level sensor and pressure protective system to make sure the machine work unattended, operation easy, safe and reliable.
Technical parameters:
Parameters
|
Unit
|
ZY-6
|
ZY-10
|
ZY-20
|
ZY-30
|
ZY-50
|
ZY-100
|
ZY-150
|
ZY-200
|
Flow rate
|
L/h
|
360
|
600
|
1200
|
1800
|
3000
|
6000
|
9000
|
12000
|
Vacuum degree
|
MPa
|
-0.06~-0.095
|
|||||||
Working pressure
|
MPa
|
≤0.3
|
≤0.4
|
≤0.4
|
≤0.4
|
≤0.5
|
≤0.5
|
≤0.5
|
≤0.5
|
Temperature range
|
°C
|
20 ~ 80
|
|||||||
Continuous working
|
H
|
150
|
|||||||
Power supply
|
|
Three phase,50HZ ,380V(or as per customer requirement)
|
|||||||
Working noise
|
dB(A)
|
60
|
61
|
63
|
70
|
70
|
75
|
70
|
70
|
Heating power
|
kW
|
9
|
11
|
13
|
15
|
30
|
48
|
58
|
70
|
Total power
|
kW
|
9.7
|
12.5
|
14.5
|
16.5
|
33.5
|
53
|
65
|
76
|
Oil inlet/outlet
|
mm
|
φ20
|
φ25
|
φ25
|
φ25
|
φ32
|
φ42
|
φ50
|
φ50
|
Weight
|
Kg
|
150
|
230
|
250
|
270
|
300
|
500
|
700
|
900
|
|
L/MM
|
970
|
1050
|
1100
|
1150
|
1200
|
1600
|
1600
|
1800
|
Size
|
W/MM
|
630
|
750
|
850
|
900
|
950
|
1000
|
1100
|
1200
|
|
H/MM
|
900
|
1300
|
1400
|
1450
|
1500
|
1800
|
1800
|
1900
|
Guarantee Value
|
|
Item
|
Guarantee indexes
|
Moisture content
|
≤5PPM
|
Impurity size
|
≤1 micron
|
Gas content
|
≤0.1%
|
Breakdown voltage
|
≥70
|