Packaging Details: | Material: PE bag & Hard paper box. |
---|---|
Delivery Detail: | in stock |
LXC9220 diesel generator set ats panel
LXC9220 plant automation controller series diesel generator sets for a single automation and control systems, the use of 32-bit microprocessors and embedded real-time systems technology, turbine automatic start / stop, a variety of parameters precision measurement, alarm protection and "three remote "function. The controller uses LCD screen (240 * 128LCD) graphic display can be displayed on one page under almost all the important parameters, save the page.
-Using 240x128LCD display with backlight, multi-language interface operations include: Chinese, English, Spanish and Russian. Can be displayed on one page most parameters, save frequently switch the page view, making the operation more convenient;
-With SMS function, when there is an alarm generator can automatically set 5 phone numbers to send alarm information can also be controlled via SMS turbine generator sets and inspection status. With advanced networking capabilities, GPRS mobile network and the Internet via the Internet, at any place where the network can be remotely monitor; (GPRS module to be installed: LXI680)
-Acquisition and display mains / generator phase voltage, phase current, phase sequence, frequency, active power, reactive power, power factor, power, various engine sensor data;
Operating Voltage | DC8.0V to DC35.0V, Continuous Power Supply. |
Power Consumption | <4W (standby ≤2W) |
Alternator Input Range: | |
3-Phase 4-Wire | 12V - 360 V AC (ph-N) |
3-Phase 3-Wire | 20V - 620 V AC (ph-ph) |
Single-Phase 2-Wire | 12V - 360 V AC (ph-N) |
2-Phase 3-Wire | 12V - 360 V AC (ph-N) |
Alternator Frequency | 50/60Hz |
Speed sensor voltage Vpp | 2.2 - 100Vpp (Peak to peak) |
Speed sensor Frequency | 10,000 Hz (max.) |
Start Relay Output | 16Amp Controller Power Voltage Output |
Fuel Relay Output | 16Amp Controller Power Voltage Output |
Programmable Relay Output 1 | 7Amp Controller Power Voltage Output |
Programmable Relay Output 2 | 7Amp Controller Power Voltage Output |
Programmable Relay Output 3 | 7Amp Controller Power Voltage Output |
Programmable Relay Output 4 | 7Amp 250VAC voltage free output |
Programmable Relay Output 5 | 7Amp 250VAC voltage free output(LXC9220) |
Programmable Relay Output 6 | 7Amp 250VAC voltage free output(LXC9220) |
Case Dimension | 254mm x 180 mm x 44 mm |
Panel Cutout | 218mm x 160mm |
C.T. Secondary | 5A rated |
Working Conditions | Temperature: (-25~+70)℃ Humidity: (20~90)% |
Storage Condition | Temperature: (-40~+85)℃ |
Protection Level | IP55: when waterproof rubber seal installed between controller and |
panel fascia. | |
IP42: when waterproof rubber seal is not installed between the | |
controller and panel fascia. | |
Insulating Intensity | Object: input/output/power |
Quote standard: IEC688-1992 | |
Test way: AC1.5kV/1min | |
leakage current: 3mA | |
Net Weight | 0.86kg |
Apply |
* Biogas Power Generation |
*Natural Gas Power |
*Field Engineering |
*Electric Power |
*Factory |
*Fire-fighting |
MOVE ADVANTAGE | |||
sales | 4000pcs/month | the fastest transit time | 2days! |
inventory situation | a lauge number of stocks | operational advantages | easy for operation |
production cycle | 1~3days |
Service |
answer all of your questions within 1day |