Type
|
Rated voltage
|
No.of cores
|
Cross Sectional Area
|
Standard
|
PV1-F
|
0.6/1 kV
|
1
|
1.5~35mm²
|
2PfG 1169/08.2007
|
Code
|
Name
|
PV1-F
|
Crosslinked polyolefin insulation crosslinked polyolefin sheath solar photovoltaic cable
|
Nominal cross sectional area (mm²)
|
(tinned copper) conductor type
|
Calculated conductor overall diameter(mm)
|
Calculated cable overall diameter(mm)
|
Calculated cable weight(kg/km)
|
Max.DC resistance at 20℃(Ω/km)
|
1.5
|
5
|
1.6
|
5.1
|
41
|
13.7
|
2.5
|
5
|
2.0
|
5.5
|
53
|
8.21
|
4
|
5
|
2.6
|
6.2
|
73
|
5.09
|
6
|
5
|
3.2
|
6.8
|
96
|
3.39
|
10
|
5
|
4.2
|
7.9
|
149
|
1.95
|
16
|
5
|
5.5
|
9.2
|
208
|
1.24
|
25
|
5
|
7.2
|
11.2
|
310
|
0.795
|
35
|
5
|
8.2
|
12.2
|
411
|
0.565
|
Nominal cross sectional area
|
Kind of installation
|
||
Single Cable free in air
|
Single Cable on surfaces
|
To cables adjacent on surface
|
|
mm²
|
A
|
A
|
A
|
1.5
|
30
|
29
|
24
|
2.5
|
41
|
39
|
33
|
4
|
55
|
52
|
44
|
6
|
70
|
67
|
57
|
10
|
98
|
93
|
79
|
16
|
132
|
125
|
107
|
25
|
176
|
167
|
142
|
35
|
218
|
207
|
176
|
Ambient temperature(℃)
|
Conversion factor
|
Up to 60
|
1.00
|
70
|
0.91
|
80
|
0.82
|
90
|
0.71
|
100
|
0.58
|
110
|
0.41
|