Diesel Generator Set Data
Set Type: XG-500GF
Standby Output: 500KW/625KVA
Prime Output: 455KW/568KVA
Rated Current: 818(A)
Rated Frequency: 50(Hz)
Start-up time: 5~6(s)
Power Factor: 0.8(Lag)
Rated Voltage: 400/230(V)
Standard Features
1. Engine: VOLVO TAD1642GE
2. Radiator 50℃ max
3. Fans are driven by belt, with safety guard
4. 24V charge alternator
5. Dry type air filter, fuel filter, oil filter
6. Alternator: single bearing alternator
7. IP23, insulation class H/H
8. Main line circuit breaker
9. Standard control panel
10. Absorber
11. Muffler
12. User manual
| Diesel Engine Data | ||
| Manufacturer: | VOLVO | |
| Model: | TAD1642GE | |
| Standby/Prime Power: | 533KW/485KW | |
| Rated Speed: | 1500(r/min) | |
| Cycle: | 4 stroke | |
| Cylinder Arrangement: | 6 in line | |
| Displacement: | 16.12L | |
| Bore and Stroke: | 144*165(mm) | |
| Compression Ratio: | 16.5:1 | |
| Governor Type: | Electronic | |
| Start battery voltage: | 24V DC | |
| Air Intake System | ||
| Air Intake System: | Turbo, Air/Air Cooling | |
| Max Intake Restriction: | 5kpa | |
| Burning Capacity: | 40.6m3/min | |
| Air Flow: | 600 m3/min | |
| Exhaust System | ||
| Exhaust Gas Flow: | 100.7m3/min | |
| Exhaust Temperature: | 494℃ | |
| Max Back Pressure: | 10kPa | |
| Fuel System | ||
| Fuel System: | Elec. Injection, Elec. Fuel System | |
| 100%( Prime Power) Load: | 201g/kwh | |
| 50%( Prime Power) Load: | 198g/kwh | |
| Oil System | ||
| Total Oil Capacity: | 48L | |
| Oil Consumption: | ≤0.11L/h | |
| Engine Oil Tank Capacity: | 42L | |
| Oil Pressure at Rated RPM: | 300-650kPa | |
| Cooling System | ||
| Cooling Way: | Water-cooled | |
| Total Coolant Capacity: | 60L | |
| Thermostat: | 86-96℃ | |
| Max Water Temperature: | 103℃ | |
| Alternator Data | ||
| Manufacturer: | STARLIGHT/STAMFORD/SIEMENS/MARATHON/ENGGA /KEPU | |
| Excitation Mode: | Brushless and self- exciting | |
| Number of phase and Access Act: | 3-phase 4-wire | |
| Connecting Type: | "Y" type connecting | |
| Alternator Capacity: | 625KVA | |
| Alternator Efficiencies: | 95% | |
| Overload: | (PRP)110% load can run 1h | |
| Protection Level: | IP22-IP23 | |
| Insulation Class, Temperature Rise: | H/H | |
| Telephone Influence Factor (TIF): | <50 | |
| THF: | <2% | |
| Voltage Regulation, Steady State: | ≤±1% | |
| Air Cooling Flow: | 1.035m3/s | |
| Altitude: | ≤1000m | |